Description:
• The eLLK 92 Ni Ex-protected " emergency" light fittings for bi-pin fluorescent lamps and equipped with an electronic ballast meet the requirements of EN 50014 to 50020, 50028 and 60598.
• The required function and duration test is performed automatically with emergency operation or requested after 6 months through the clearly visible red LED indicator. |
Technical Data
eLLK 92 Ni, eLLM 92 Ni |
| Type of Protection: |
EEx edm ib II C T4 |
| EC-Type Examination Certificate: |
PTB 96 ATEX 2144 |
| Marking to 94/9/EC |
Ex II 2 G / Ex II 2 D |
| Enclosure Material: |
Polyester reinforced |
| Protective Bowl: |
Polycarbonate |
| Rated Voltage: |
AC: 220 - 254 V ± 10%, 47 - 63 Hz
DC: 110 - 127 V ± 10%, 47 - 63Hz (on request) |
| Degree of Protection: |
IP 66 to EN 60529 (corresponds to IEC 529) |
| Protection Class: |
1 |
| Permissible Ambient Temp. |
-5 °C to +50 °C |
| Cable Entries: |
2 x EEx e cable entry M25 x 1.5
for cables from Ø 8 - 17 min,
1 x EEx e blanking plug |
| Connection Terminals: |
L1, L2, L3 L, N, PE; max. 2 x 6 mm²
single wire per terminal |
| ILLuminant: |
Bi-pin lamps: 18 W (G13 - 81 - IEC - 1105 - 1)
36 W (81 - IEC 1305-2) |
| Weight: |
Approx. 10.0 kg (2 x 18 W )
approx. 12.0 kg (2 x 36 W) |
| Rated emergency lighting operation: |
1 lamp
Can be sent on site for an emergency lighting duration of 1.5 or 3 hours Battery set 2710-10-02 with LED display and monitoring with microprocessors. |
|
|
|
|
|
 |
|