Ex-29 Control and selection Switch with Measuring Instrument |
| Marking to 94/9EC: |
Ex II 2 G / Ex II 2 D (applied for) |
| Type of Protection:: |
EEx ed IIC T6
|
| EC-Type Examination certificate : |
PTB 99 ATEX 1163 |
| Enclosure Material: |
Impact-resistant polyester, reinforced |
| Degree of Protection: |
IP 66 to EN 60529 |
| Rated Voltage: |
Up to 500 V |
| Rated Current: |
16 A |
| Switching Capacity: |
AC 15 DC 13 up to 60 V 2.0 A
Up to 230 v 6 A up to 110 V 0.6 A
Up to 400 V 4 A up to 230 V 0.5 A |
| Connection Terminals: |
Up to 1 x 6 mm² or 2 x 2.5 mm² |
| Measuring Instrument: |
Type of current DC and AC
Accuracy Class 2.5
Movement Ct connection
Scale Standard 0 - 100 / 150%
Overload Range: 1 : 1.5 (indicated)
Terminals Up to 2 x 4 mm² |
| Cable Entry: |
Standard 1 x M32 for cable diameters 12 - 21 mm
gland plate in brass design for metal cable entries on request |
| Weight |
1.9 kg |