Description: Heavy duty rubber sheathed flexible cables are suited for use for medium mechanical stress in dry, damp and wet areas as well as in open air and in agriculture plants.
Application:
• Industrial equipment such as boilers, heating plates, hand lamps
• Electric tools such as drills, circular saws
• Homework tools
• Transportable motors or machine at site • Fixed installation on plaster
• Temporary buildings
• Residential barracks
• Lifts and cranes
Technical Data: HO7 RN-F to DIN VDE 0282 part 4, HD 22.4 S3 IEC 60245-4
Temperature Range : -30 C° to +60 C°
Permissible operating temperature : at conductor +60 C°
Nominal voltage: U0 / U 450 / 750 V in case of protected and fixed installation U0 / U 600 / 1000 V
Max permissible operating voltage in three phase and one phase a.c. system
U0 / U 619/1238 V
Test voltage 2500 V
Permanent tensile load max. 15 N / MM²
Minimum bending radius for fixed installation 4x cable Ø for guiding over roller 7.5x cable Ø
during winding on drums 5-7x cable Ø