Description: Suitable for installation in indoors and in cable ducts, outdoors as well as for laying on racks for industrial and switching systems and power plants. Limited use when buried in the earth if the PVC outer jacket could be damaged by high mechanical stress.
The inner conducting layer between the conductor and the XLPE insulation and the firmly bonded outer conducting layer on the XLPE insulation assures a construction free of partial discharges with high operational reliability.
Application:
• Indoor Installation
• In Water
• Indoor Ducts
• Cable Tray for Industries
• Outdoor
• Switch Board
• Underground
• Power Stations
Technical Data: Three core XLPE-insulated power cables to VDE 0273 and IEC 60502
Temperature range: during installation up to -5 °C
Operating Temperature: max. 90 °C
Short circuit temperature: Core 250 °C, Screen 350 °C (duration)
(short circuit duration up to 5 sec.)
Nominal voltage: U0 / U 0.6 / 10 kV
Operating voltages: max. 12 kv
Test voltages: 15 kv
Test voltage d.c.: 48 kv
Minimum bending radius: max. 15 x cable Ø
Test: According to DIN VDE 0273 und IEC 60502
Properties:
The materials used in manufacture are cadmium free and contain no silicone and free from substances harmful to the wetting properties of lacquers.